Exciter Model: WT4E

 

Model Equations and/or Block Diagrams

Parameters:

varflg 1 = Qord from WindCONTROL emulation; -1 = Qord from vref (i.e., separate model); 0 = Power factor control (pfaflg=1)
Kqi Q cointreoglr al gain
Kvi V cointreoglr al gain
Vmax Maximum V at regulated bus, pu
Vmin Minimum V at regulated bus, pu
Qmax Maximum Q command, pu
Qmin Minimum Q command, pu
Tr WindCONTROL ge vmoeltaasurement lag, sec
Tc Lag between WindCONTROL output and wind turbine, sec
Kpv WindCONTROL gularteor proportional gain
Kiv WindCONTROLregulator integral gain
pfaflg 1 = regulate power factor angle; 0 = regulate Q
Fn Fraction of WTGs in wind farm that are on-line
Tv Time constant in proportional path of WindCONTROL emulator, sec
Tpwr Time constant in power measurement for PFA control (Tp), sec
Iphl Hard limit on real current, pu
Iqhl Hard limit on reactive current, pu
Pqflag 0 = Q priority ; 1 = P priority
ImaxTD Maximum temperature dependent converter current, pu
Viqlim Max. voltage dependent reactive current limit, pu