Exciter Model: WT4E
Following checks and corrections are applied during Validation and AutoCorrection.
- If 0.0 < Tr < 0.25*Mult*TimeStep then Tr = 0.0
ElseIf 0.25*Mult*TimeStep < Tr < 0.5Mult*TimeStep then Tr = 0.5*Mult*TimeStep - If 0.0 < Tv < 0.5*Mult*TimeStep then Tv = 0, ElseIf 0.5*Mult*TimeStep < Tv < Mult*TimeStep then Tv = Mult*TimeStep
- If 0.0 < Tp < 0.5*Mult*TimeStep then Tp = 0, ElseIf 0.5*Mult*TimeStep < Tp < Mult*TimeStep then Tp = Mult*TimeStep
- If 0.0 < Tpwr < 0.5*Mult*TimeStep then Tpwr = 0, ElseIf 0.5*Mult*TimeStep < Tpwr < Mult*TimeStep then Tpwr = Mult*TimeStep
- If Vmax < Vmin then swap the values
- If Qmax < Qmin then swap the values
Mult represents the user-specified value Minimum time constant size as multiple of time step option on the Validation page of the Transient Stability Dialog
TimeStep represents the integration time step being used as described on TimeStep
Following treatment is handled during the transient numerical simulation
- If QCmd > Qmax , then Qmax = QCmd or if QCmd < Qmin , then Qmin = QCmd
- If VRef > Vmax , then Vmax = VRef or if VRef < Vmin, then Vmin = VRef
Model Equations and/or Block Diagrams
Parameters:
| varflg | 1 = Qord from WindCONTROL emulation; -1 = Qord from vref (i.e., separate model); 0 = Power factor control (pfaflg=1) |
| Kqi | Q cointreoglr al gain |
| Kvi | V cointreoglr al gain |
| Vmax | Maximum V at regulated bus, pu |
| Vmin | Minimum V at regulated bus, pu |
| Qmax | Maximum Q command, pu |
| Qmin | Minimum Q command, pu |
| Tr | WindCONTROL ge vmoeltaasurement lag, sec |
| Tc | Lag between WindCONTROL output and wind turbine, sec |
| Kpv | WindCONTROL gularteor proportional gain |
| Kiv | WindCONTROLregulator integral gain |
| pfaflg | 1 = regulate power factor angle; 0 = regulate Q |
| Fn | Fraction of WTGs in wind farm that are on-line |
| Tv | Time constant in proportional path of WindCONTROL emulator, sec |
| Tpwr | Time constant in power measurement for PFA control (Tp), sec |
| Iphl | Hard limit on real current, pu |
| Iqhl | Hard limit on reactive current, pu |
| Pqflag | 0 = Q priority ; 1 = P priority |
| ImaxTD | Maximum temperature dependent converter current, pu |
| Viqlim | Max. voltage dependent reactive current limit, pu |